DF-TV7 UV2IR Flame Detector (SIL2)

The Simtronics DF-TV7 is a combined ultraviolet / infrared flame detector offering excellent flame detection whilst maintaining outstanding false alarm immunity.  The UV/2IR Multi Flame DF-TV7  is designed to respond to unwanted hydrocarbon fires, whilst maintaining a high degree of false alarm immunity. The DF-TV7 flame detector uses combined ultraviolet/infrared (UV-2IR) optical technology that provides industry-leading immunity to false alarms based on the two IR channel design. 

The device offers a wide range of output options, as standard and is suitable for use in SIL 2 applications. The detector can be configured to communicate with a wide range of fire panels, controllers, and PLCs and offer HART 7 and Syntel (Lonworks) protocols for addressable event monitoring. The devices come standard with a configurable 4-20mA or 0-22mA (PLC) output, two configurable alarm relays, and two detector status LEDs. 

All Multi Flame detectors are equipped with a continuous optical lens auto-check to ensure that the optical path is clear and that the detector functions properly. Sensors can be replaced easily in the field without removing any cable glands. Devices are easy to test and configure using a TLU wireless handheld unit that is approved for use in hazardous areas. The TLU can also be used for wireless testing of the optical and output circuits. The TLU can also be used for wireless testing of the optical and output circuits. 

Description

Technical Description – DF-TV7 UV2IR Flame Detector (SIL2)

The MultiFlame DF-TV7–V is a combined ultraviolet /infrared flame detector offering excellent flame detection whilst maintaining outstanding false alarm immunity and is suitable for use in SIL 2 applications 

A Closer Look

  • Continuous auto-check of optical lens  
  • Relays, 4-20mA, 0-22mA, Hart outputs
  • Long range up to 80m, 260 ft deep 
  • Wide field of view 120° 
  • SIL2 

All Simtronics Multi Spectrum Flame detectors are equipped with a continuous optical lens integrity auto-check to ensure that the optical path is clear and that the detector functions properly. Sensors can be replaced easily in the field without removing any cable glands. 

Teledyne Oldham Simtronics DF-TV7 UV2IR Flame Detector (SIL2)

Control System Integration

The DFTV7 may be interfaced directly with a wide range of fire panels, controllers and PLC’s etc. The flame detector unit is fully configurable using a wireless hand-held terminal (TLU) or optionally via HART (R) giving true flexibility to the installer. Time delays, sensitivity and output configuration are all set up via the TLU; a hazardous area approved hand-held unit. Wireless testing of the optical and output circuits is also possible using the TLU. 

The Specs at a Glance

Technology                                         Multi-spectrum ultraviolet dual infra-red

Fire types                                            Hydrocarbon fires

Range, n-heptane                            45M (147ft) 0.3X0.3M (1 sq ft)

Range, gasoline                                 35M (114 0ft) 0.3X0.3M (1 sq ft)

Field of view                                       Horizontal angle @ 50% 97°

Vertical angle @ 50% 55°

Response time                                  Adjustable from 2 to 20 seconds (typical 3.5S.)

Warranty                                             2 Years, back to factory

Output signal

Standard                                              4-20Ma or 0-22ma (configurable by the user)

Max. Load impedance 700 ω (std. )

Hart protocol 7th edition (option)

Alarms                                                  2 X configurable relays max 1a / 30vcc

Visual                                                    Normal operating, alarm, fault

Electrical

Power supply                                     24 Vdc, range (18 – 28 vdc)

Power consumption                        2W normal, 4w during test

Connection                                         0.3 Mm2 (22 awg) – 1.5 Mm2 (16 awg)

Shielded cable recommended

Environmental

Storage                                                De -40°c à +70°c

Operation                                            -40°C to +65°c (-40°f to 149°f)

Option                                                  Sunshade, max. Temp. 85°C (185°f)

Humidity                                              99% Rh (non-condensing)

Ingress                                                  IP66

RFI /EMI                                               Complies with en50130-4

Explosion proof housing

TLU600                                                 316 L stainless steel

Weight                                                 5KG (10 LBS)

Dimensions                                         246.8 X 140.4 X 115 mm (l, h, w)

9.8 X 5.5 X 4.5 Inches

Data Sheet – DF-TV7 UV2IR Flame Detector (SIL2)

IECEx Certificate of Conformity

Hover Box Element

Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Certificate of Registration HCF Verified

Hover Box Element

Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

SIL Certificate

Hover Box Element

Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

ATEX Certificate

Hover Box Element

Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Wireless Configuration Tool

Hover Box Element

LT15 Test Lamp for DMTV Series

Hover Box Element