Description
Technical Description: OmniGraud 660 – Flame Detector
The Omniguard® model 660 UV flame detector is designed to detect fires and output appropriate alarm information. The model 660 senses ultraviolet radiation in the appropriate wavelength for extremely fast fire detection. The model 660 will sense both hydrocarbon and non-hydrocarbon fires, a technology which has proven itself over decades of reliable service.
Key Features:
- Available in special high temperature version, -40°C to +125°C (-40°F to +257°F)
- Five-year warranty on sensors from date of delivery, three-year warranty on components or manufacturing defects from date of delivery
- Field of view 120°
- Robust, weatherproof enclosure for indoor or outdoor applications
- FM, CSA, IECEx, ATEX, SIL2, UKCA, ECAS-Ex, PESO
- Advanced through-thelens diagnostic self-test
- Long range detection
- Self-contained, explosion- proof enclosure
- Field configurable relays and sensitivity
- State-of-the-art microprocessor control
- High intensity, localized indication of fire or fault
Specs at a Glance:
| Detector inputs
|
|
| Inputs: | |
| nominal voltage | 24 VDC (ripple voltage <240 mV) |
| range | 20 to 32 VDC |
|
Power consumption, standard version
|
|
| standby | 42 mA |
| standby 4-20 mA | 47 mA |
| alarm | 56 mA |
| auto test | 136 mA |
| manual test | 159 mA |
|
Power consumption, high temp version
|
|
| standby | 56 mA |
| alarm | 94 mA |
| auto test | 140 mA |
| manual test | 193mA |
|
Detector outputs
|
|
| Inputs: | |
| relays (2) | fire, trouble, dry contacts, hermetically sealed |
| fire relay | user selectable latching or non-latching |
| rated (standard) | 2 A at 30 VDC, User selectable NO or NC |
| rated (high temp.) | 4 A at 30 VDC, User selectable NO or NC |
| Current loop (standard version) 0 to 20 mA output | |
| 20 mA = | Fire |
| 4 mA = | Normal |
| 3 mA = | Fire relay coil fault |
| 2 mA = | EEPROM corrupted fault |
| 1 mA = | Self-test fault |
| 0 mA = | Current loop fault |
| RS485 User Interface (UI) | |
|
Mechanical considerations
|
|
| Weight | 2.4 kg (5 lbs) (aluminum) 6.3 kg (13 lbs) (stainless steel) |
| Height x width x depth | 114 x 140 x 153 mm (4.5 x 5.5 x 6.0 in) |
| Conduit entry | 3/4-14 NPT or M20-1.5 |
| Optional accessories | Art.no |
| Swivel mount (SS304) | 20856 (for aluminum detectors) |
| Pole mount 2″ (SS316L) | 26803 (for swivel mount 20856) |
| Swivel mount (SS316) | 24784 (for stainless steel detectors) |
| Pole mount 2″ | (SS316L) 26803 (for swivel mount 20856) |
| Swivel mount (SS316) | 24784 (for stainless steel detectors) |
| Pole mount 2″ (SS316L) | 26807 (for swivel mount 24784) |
| Rain shield/ Sun shield (SS316L) | 23546 |
| Air shield assembly | 8001023 (for standard temp. detectors) |
| Air shield assembly | 26489 (for high temp. detectors) |
| Portable test unit | 43808-2 (115VAC, CSA approved) |
| 43808-3 (100-240VAC, CE approved) |
Data Sheet - Omniguard 660
Hover Box Element
Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.
Certificate of Conformity