Description
Technical Description – STExC1X05F Alarm Horn & Xenon Strobe
Features
- Robust corrosion proof 316L stainless steel enclosure
- High output; up to 117dB(A)
- 4 remotely selectable alarm stages/channels
- Positive or negative line stage/channel switching
- Choice of 64 alarm tone frequencies
- User selectable strobe flash rates
- Field replaceable lens colour filter
- Automatic synchronisation on multi-beacon & sounder systems
- Continuously rated
- Compact form factor
- Stainless steel fixings
- Ratchet adjustable 316 stainless steel bracket
- 316 Stainless steel stopping plugs included
- 3 x cable entries
- Duplicate cable terminations (in & out for daisy-chain installations)
- Available with custom tone configurations and frequencies
Specification
Alarm Horn: | |
---|---|
Maximum output: | 117dB(A) @ 1 metre [108dB(A) @ 10ft/3m] |
Nominal output: | 113dB(A) @ 1m +/- 3dB – Tone 2 [104dB(A) @ 10ft/3m] |
No. of tones: | 64 (UKOOA / PFEER compliant) |
No. of stages: | 4 |
Volume control: | Adjustable -12dB(A) |
Effective range: | 125m/410ft @ 1KHz |
Supply Voltages: | 24Vdc; 115Vac; 230Vac |
Stage switching: | DC units: negative or positive AC units: common supply line |
Strobe Beacon: | |
Energy: | 5 Joules (5Ws) |
Flash rates: | Option 1: 1Hz (60 fpm) Option 2: 1.5Hz (90 fpm) Option 3: Double Strike |
Peak Candela: | 500,000 cd – calculated from energy (J) |
Eff. Intensity: | 250 cd – calculated from energy (J) |
Peak Candela: | 46,976 cd* – measured ref. to I.E.S. |
Eff. Intensity: | 143 cd* – measured ref. to I.E.S. |
Lens colours: | Amber, Blue, Clear, Green, Magenta, Red & Yellow |
Tube life : | Emissions are reduced to 70% after 5 million flashes |
General: | |
Ingress protection: | EN60529: IP66 |
Enclosure matl: | 316L Stainless Steel |
Enclosure finish: | Chromated & powder coated |
Colour: | RAL3000 Red |
Cable entries: | 3 x M20 ISO (2 x stopping plugs supplied) Adaptors to M25, 1/2″ & 3/4″ NPT can be specified |
Terminals: | 0.5 – 2.5mm² (20-14 AWG) |
Enclosure volume: | <2 litres |
Line monitoring: | Blocking diode included EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor or diode (DC versions) can be fitted |
Grounding stud: | M5 |
Temperature range: | -50° to +70°C (-58°F to +158°F) |
Relative humidity: | 95% – Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist |
Weight: | 7.45kg/16.42lbs |
Current Consumption
Voltage: | Range: | Alarm Horn | Xenon Strobe | Combined | ||||
---|---|---|---|---|---|---|---|---|
12V dc | 10-14Vdc | 146mA | 678mA | 824mA |24V dc |
20-28Vdc | 185mA | 323mA | 508mA |
48V dc | 42-54Vdc | 138mA | 198mA | 336mA |230V ac |
220-240Vac 50/60Hz |
21mA | 79mA | 106mA |
Nominal current. Alarm horn sounder: Tone 2, Xenon Strobe: 1Hz Flash Rate |
Effective Candela Lens Colour Factor
Amber | Blue | Clear | Green | Red | Yellow |
0.70 | 0.24 | 1.00 | 0.25 | 0.23 | 0.93 |
Please refer to datasheet for more information
Manual - STExC1X05F Alarm Horn & Xenon Strobe
Hover Box Element
Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.
IECEx Certificate of Conformity
Hover Box Element
Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.
ATEX Certificate
Hover Box Element
Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.
EU Declaration of Conformity
Hover Box Element
Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.