PhaseGuard ST 40

In-line Phase Switch for Turbidity

The PhaseGuard ST 40 measures the phase transitions for turbidity. Two models of the PhaseGuard cover the possible applications: Phase switch for turbidity (PhaseGuard ST 40 – S) and for very high turbidity (PhaseGuard ST 40 – H). The PhaseGuard ST 40 is equipped with an optimised universal measuring range in absorption percent. Simple configuration and communication via one of the available interfaces, from 4…20 mA current interfaces to bus systems, guarantee simple application and system integration. The PhaseGuard ST 40 comes in a new, fresh design with an integrated colour touchscreen display. This makes the PhaseGuard ST 40 easy to identify in the system. The status is displayed directly in the device at the measuring point. The security of the data on the new interfaces is guaranteed.

Sigrist Photometer

Category: Tag:
Send Enquiry

Description

Technical Description – PhaseGuard ST 40

In-Line Phase Switch for Turbidity

The PhaseGuard ST 40 measures the phase transitions for turbidity. Two models of the PhaseGuard cover the possible applications: Phase switch for turbidity (PhaseGuard ST 40 – S) and for very high turbidity (PhaseGuard ST 40 – H). The PhaseGuard ST 40 is equipped with an optimised universal measuring range in absorption percent. Simple configuration and communication via one of the available interfaces, from 4…20 mA current interfaces to bus systems, guarantee simple application and system integration. The PhaseGuard ST 40 comes in a new, fresh design with an integrated colour touchscreen display. This makes the PhaseGuard ST 40 easy to identify in the system. The status is displayed directly in the device at the measuring point. The security of the data on the new interfaces is guaranteed.

A Closer Look

Advantages

  • In-Line Sensing – proven solution for phase detection through turbidity
  • Real-Time Monitoring with very short response time
  • Process Optimization & Control, CIP-Monitoring
  • Permanent device monitoring in the background
  • Extremely low maintenance e.g. due to seal-less design
  • Cost efficiency & high reliability
  • Coloured display and simple configuration directly on the device
  • Simple configuration directly on the device and easy system integration
  • Hygienic design according to EHEDG and compliant to Regulation (EC) No 1935/2004 on materials and articles intended to come into contact with
    food
  • Swiss Engineering / Swiss Made

Typical Applications include:

  • Monitoring and controlling of interfaces in beverages such as beer, fruit juices, etc.
  • Optimization of beer / yeast separation steps
  • Monitoring of clean in pipe processes (CIP), e.g. in the dairy industry
  • Minimizing product losses and increasing yields
  • Recognition of interfaces for product change over or product push-out
  • Faster processing time due to better resolution of start-stop conditions

Specs at a Glance

Measuring principal Absorption
Wavelength 870mm
Measuring range 0..100%
Resolution 0.5 % Absorption
Accuracy +/-1% Absorption *
Response time < 0.3 s at 0 Seconds Integration time (Step response -limit value switch)
Path length 10 mm (Modell

PhaseGuard ST 40 S2XX – 0000)

5 mm (Modell

PhaseGuard ST 40 H2XX – 8000)

Medium temperature -10 … +100 °C

-10 … +85°C at ambient temperature

55°C

-10 … +75°C at ambient temperature

60°C

Cleaning surroundings CIP/SIP- compatible up to 120 °C @2h

-10 … +50 °C

0 … 100 % relative humidity

Medium pressure Max. 1 MPa (10 bar) @100 °C
Pipe connections Inline VARINLINE® – housing or compatible

DN 40 … DN 150, 1 1/2“… 6“

Operating voltage 24 VDC ± 10 % (Interface PoE according to standard)
Warm up time < 3 min
Power consumption Max. 3 W
Protection class IP 66
Dimensions Ø 100.5 x 137 mm
Material Housing: Stainless steel 1.4301 / AISI 304

Sensor head material: Stainless steel

1.4404 / AISI 316L

Window material: Sapphire

Touchscreen: Soda-Lime tempering glas

Weight 1.5kg
Display Display: 2.4“ with Touchscreen

Resolution: 320 x 240 Pixel

Interfaces
LT (Standard) 1 Current output 0/4 … 20 mA,

max. 700 Ohm, 1 digital input, 2 digital outputs

IO 6 configurable inputs/outputs: – Max. 2 digital inputs: 5 … 28 VDC – Max. 4 digital outputs: High-Side Switch max. 20 mA – Max. 4 current outputs: 0/4 … 20 mA, max. 700 Ohm – Modbus RTU
PoE Ethernet LAN connection with Power over Ethernet:        – Ethernet according to 10/100BaseT

– POE according to 802.3af, Class 0

– Sigrist Web interface

Profibus Profibus DP-V1 Slave
Profinet Profinet IO, Conformity class B
* in reference to factory standard

Data Sheet - PhaseGuard ST 40

PhaseGuard ST 40

Hover Box Element

PhaseGuard ST 40 - Turbidity at Separator

Hover Box Element

PhaseGuard ST 40 - Phasen Separation - Beer/ Water

Hover Box Element

PhaseGuard ST 40 - Phasen Separation. Yeast/Beer

Hover Box Element

Sigrist Communication Software

Software for Sigrist devices of the Edge generation

Available upon request.